5. Unit Protector
1) ApplicationUnit protector ( type: GRT-1 pair) consists of gas discharge tube, PTC, fuse, LED, metal reed and fire-retardant plastic cover. It is used in the IDC termination module for one-pair line's protection against over-voltage and over-current, and it also has the functions of fail safe and LED lighting alarming.
2) Main Technical Data
a) Plastic Material: flame-retardant ABS ( conforming to GB4609/FV-0 grade or UL94V-0);
b) Insulation Resistance: more than 1000Mohm;
c) Contact Resistance: less than 7mohm;
d) DC Spark-over Voltage(100v/s): 190v~260v;
e) Impulse Spark-over Voltage(1kv/µs): less than or equal to 800v;
f) Fail Safe: earthing within 15 seconds when discharging current reachs 2.5Amps;
g) Alarming: LED lighting after operation of fail safe device;
h) Overcurrent Protection: non-operation lasting for 60 seconds under current 110mA ( 60VDC) ;
i) Normal Resistance : < 22 ohm
j) Resistance Difference between line a and line b : < 2 ohm
k) Current-Restriction Characteristics:
Current (A)
Operation Time (seconds)
0.50
not more than 20.0
0.75 not more than 5.0 1.00
not more than 1.5
2.00 not more than 0.5 3.00 not more than 0.2
3) Accessories10 pieces of unit protectors will share 1 piece of earthing bar.
Click here to go on to "6. Insertion Tool For IDC Termination Module"
Click here to go back to "PRODUCT LIST"
HIGHWAVE TELECOM
E-mail(1): highwave@szonline.net
E-mail(2): marketing@highwavetele.com
¡¡